Skip to Content

Dry cooler BC/BD-2x780EB1-B01 C

Dry cooler BC/BD-2x780EB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x780EB1-B01 C

Heat rejection i
714.54 kW
Air flow
248,436 m³/h
Fans
14 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 248,436 m³/h
External surface 1,915.5 m²
Inner volume 419.5 dm³
Fin materialAluminium
Net weight 2,211 kg
Fans
Quantity 14
Diameter 800 mm
Speed 900 rpm
Power 25,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x780EB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
714.543 kW Fluid flow 124.01 m³/h Pressure drop 17.7 kPa
Heat rejection · Low speed (Y)
566.700 kW Fluid flow 98.35 m³/h Pressure drop 11.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 396.29 not rated not rated not rated not rated not rated
40 714.54 400.64 not rated not rated not rated not rated
45 1024.78 716.83 404.43 not rated not rated not rated
50 1332.35 1025.43 719.03 407.89 not rated not rated
55 1638.76 1331.55 1026.27 721.36 411.29 not rated
60 1944.43 1636.50 1331.20 1027.70 724.10 414.75

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 317.06 not rated not rated not rated not rated not rated
40 566.70 320.43 not rated not rated not rated not rated
45 808.77 568.14 323.34 not rated not rated not rated
50 1048.39 808.70 569.50 326.05 not rated not rated
55 1286.86 1047.00 808.89 571.08 328.61 not rated
60 1524.70 1284.20 1046.07 809.63 572.92 331.23

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 714.543 124.01 17.7
Low speed (Y) 566.700 98.35 11.6

Dimensions

Dimension drawing of BC/BD-2x780EB1-B01 C
Dimension drawing
Dimensions as drawn
A 10350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9900 mm
H 1400 mm
I 2310 mm
K 10850 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 10350 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.