Skip to Content

Dry cooler BC/BD-2x791EB5-B04 C

Dry cooler BC/BD-2x791EB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x791EB5-B04 C

Heat rejection i
745.31 kW
Air flow
342,845 m³/h
Fans
14 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 342,845 m³/h
External surface 1,706.3 m²
Inner volume 301.2 dm³
Fin materialAluminium
Net weight 2,174 kg
Fans
Quantity 14
Diameter 910 mm
Speed 840 rpm
Power 39,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 70.0 dB(A)
Sound power 103.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x791EB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
745.312 kW Fluid flow 129.35 m³/h Pressure drop 43.6 kPa
Heat rejection · Low speed (Y)
607.532 kW Fluid flow 105.45 m³/h Pressure drop 30.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 415.23 not rated not rated not rated not rated not rated
40 745.31 418.90 not rated not rated not rated not rated
45 1069.54 747.67 422.13 not rated not rated not rated
50 1391.98 1070.79 749.87 425.08 not rated not rated
55 1713.56 1392.20 1072.12 752.09 427.89 not rated
60 2034.67 1712.80 1392.72 1073.72 754.48 430.73

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 340.95 not rated not rated not rated not rated not rated
40 607.53 344.00 not rated not rated not rated not rated
45 868.56 609.37 346.67 not rated not rated not rated
50 1127.83 869.45 611.14 349.14 not rated not rated
55 1386.35 1127.90 870.49 612.99 351.53 not rated
60 1644.38 1385.56 1128.27 871.86 615.06 353.97

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 745.312 129.35 43.6
Low speed (Y) 607.532 105.45 30.2

Dimensions

Dimension drawing of BC/BD-2x791EB5-B04 C
Dimension drawing
Dimensions as drawn
A 10350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9900 mm
H 1400 mm
I 2310 mm
K 10850 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 10850 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.