Skip to Content

Dry cooler BC/BD-2x880AB5-B03 C

Dry cooler BC/BD-2x880AB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x880AB5-B03 C

Heat rejection i
429.18 kW
Air flow
144,138 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 144,138 m³/h
External surface 1,671.5 m²
Inner volume 269.1 dm³
Fin materialAluminium
Net weight 2,153 kg
Fans
Quantity 16
Diameter 800 mm
Speed 435 rpm
Power 5,100 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 44.0 dB(A)
Sound power 77.0 dB(A)
Energy class C
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x880AB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
429.179 kW Fluid flow 74.49 m³/h Pressure drop 18.3 kPa
Heat rejection · Low speed (Y)
342.289 kW Fluid flow 59.41 m³/h Pressure drop 12.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 243.20 not rated not rated not rated not rated not rated
40 429.18 245.24 not rated not rated not rated not rated
45 610.20 430.02 247.01 not rated not rated not rated
50 789.68 610.12 430.85 248.65 not rated not rated
55 968.42 788.76 610.22 431.79 250.28 not rated
60 1146.79 966.72 788.20 610.66 432.99 251.95

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 195.40 not rated not rated not rated not rated not rated
40 342.29 197.02 not rated not rated not rated not rated
45 484.60 342.77 198.41 not rated not rated not rated
50 625.50 484.27 343.22 199.66 not rated not rated
55 765.72 624.41 484.03 343.81 200.90 not rated
60 905.55 763.91 623.58 484.10 344.60 202.21

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 429.179 74.49 18.3
Low speed (Y) 342.289 59.41 12.2

Dimensions

Dimension drawing of BC/BD-2x880AB5-B03 C
Dimension drawing
Dimensions as drawn
A 10150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 1200 mm
I 2310 mm
K 10650 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.