BC/BD-2X580AC5-B01 C
489.44 kW
Defrost: None
Product code: BC/BD-2x880DC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 125,771 m³/h |
|---|---|
| External surface | 2,118.7 m² |
| Inner volume | 488.0 dm³ |
| Fin material | Aluminium |
| Net weight | 2,383 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 5,100 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | C |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2x880DC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 296.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 489.49 | 296.55 | not rated | not rated | not rated | not rated |
| 45 | 677.88 | 488.77 | 296.90 | not rated | not rated | not rated |
| 50 | 864.63 | 676.25 | 488.36 | 297.43 | not rated | not rated |
| 55 | 1050.62 | 862.14 | 675.15 | 488.40 | 298.15 | not rated |
| 60 | 1236.21 | 1047.30 | 860.40 | 674.77 | 489.03 | 299.35 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 226.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 369.84 | 226.50 | not rated | not rated | not rated | not rated |
| 45 | 509.68 | 369.64 | 226.99 | not rated | not rated | not rated |
| 50 | 648.23 | 508.96 | 369.71 | 227.67 | not rated | not rated |
| 55 | 786.18 | 647.03 | 508.69 | 370.18 | 228.58 | not rated |
| 60 | 923.82 | 784.52 | 646.45 | 509.03 | 371.18 | 229.83 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 489.491 | 84.89 | 83.1 |
| Low speed (Y) | 369.838 | 64.14 | 50.6 |
| A | 10150 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9700 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 10650 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.