Dry cooler BC/BD-2x891EB5-B04 C

Dry cooler BC/BD-2x891EB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x891EB5-B04 C

Heat rejection i
861.60 kW
Air flow
391,823 m³/h
Fans
16 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 391,823 m³/h
External surface 1,950.1 m²
Inner volume 331.0 dm³
Fin materialAluminium
Net weight 2,473 kg
Fans
Quantity 16
Diameter 910 mm
Speed 840 rpm
Power 44,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 71.0 dB(A)
Sound power 104.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x891EB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
861.600 kW Fluid flow 149.53 m³/h Pressure drop 63.4 kPa
Heat rejection · Low speed (Y)
701.998 kW Fluid flow 121.84 m³/h Pressure drop 44.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 484.66 not rated not rated not rated not rated not rated
40 861.60 488.23 not rated not rated not rated not rated
45 1232.01 863.79 491.40 not rated not rated not rated
50 1600.39 1233.00 865.88 494.37 not rated not rated
55 1967.80 1600.26 1234.14 868.04 497.19 not rated
60 2334.69 1966.58 1600.50 1235.69 870.50 500.06

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 397.82 not rated not rated not rated not rated not rated
40 702.00 400.73 not rated not rated not rated not rated
45 1000.12 703.69 403.34 not rated not rated not rated
50 1296.34 1000.79 705.36 405.78 not rated not rated
55 1591.63 1296.06 1001.68 707.17 408.19 not rated
60 1886.43 1590.45 1296.22 1002.97 709.29 410.74

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 861.600 149.53 63.4
Low speed (Y) 701.998 121.84 44.0

Dimensions

Dimension drawing of BC/BD-2x891EB5-B04 C
Dimension drawing
Dimensions as drawn
A 11750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 11300 mm
H 1400 mm
I 2310 mm
K 12250 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 12250 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.