BC/BD-t-2X163AD5-B01 C
65.85 kW
Defrost: None
Product code: BC/BD-350DC1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 19,839 m³/h |
|---|---|
| External surface | 235.3 m² |
| Inner volume | 28.7 dm³ |
| Fin material | Aluminium |
| Net weight | 267 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,100 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-350DC1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 37.72 | not rated | not rated | not rated | not rated | not rated |
| 40 | 65.91 | 37.98 | not rated | not rated | not rated | not rated |
| 45 | 93.31 | 65.95 | 38.20 | not rated | not rated | not rated |
| 50 | 120.44 | 93.18 | 66.01 | 38.40 | not rated | not rated |
| 55 | 147.45 | 120.16 | 93.10 | 66.09 | 38.61 | not rated |
| 60 | 174.40 | 147.02 | 119.95 | 93.08 | 66.22 | 38.84 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 65.907 | 11.44 | 27.7 |
| A | 2700 mm |
|---|---|
| B | 1200 mm |
| C | 920 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2500 mm |
| H | 800 mm |
| I | 870 mm |
| K | 3000 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3000 mm |
|---|---|
| Width | 920 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.