BC/BD-t-180JC1-B01 C
73.59 kW
Defrost: None
Product code: BC/BD-363BB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 25,992 m³/h |
|---|---|
| External surface | 209.4 m² |
| Inner volume | 29.8 dm³ |
| Fin material | Aluminium |
| Net weight | 294 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 79.3 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-363BB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 42.12 | not rated | not rated | not rated | not rated | not rated |
| 40 | 73.76 | 42.38 | not rated | not rated | not rated | not rated |
| 45 | 104.64 | 73.81 | 42.60 | not rated | not rated | not rated |
| 50 | 135.29 | 104.54 | 73.87 | 42.80 | not rated | not rated |
| 55 | 165.83 | 135.03 | 104.46 | 73.95 | 43.00 | not rated |
| 60 | 196.31 | 165.43 | 134.83 | 104.43 | 74.07 | 43.21 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 73.758 | 12.80 | 39.1 |
| A | 3050 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 3300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.