Product code: BC/BD-363CC5-B19 C

Heat rejection i
101.86 kW
Air flow
34,060 m³/h
Fans
3 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 34,060 m³/h
External surface 313.4 m²
Inner volume 44.1 dm³
Fin materialAluminium
Net weight 347 kg
Fans
Quantity 3
Diameter 630 mm
Speed 1,330 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-363CC5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
101.861 kW Fluid flow 17.68 m³/h Pressure drop 41.5 kPa
Heat rejection · Low speed (Y)
86.372 kW Fluid flow 14.99 m³/h Pressure drop 30.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 58.26 not rated not rated not rated not rated not rated
40 101.86 58.57 not rated not rated not rated not rated
45 144.43 101.89 58.84 not rated not rated not rated
50 186.67 144.21 101.92 59.10 not rated not rated
55 228.75 186.21 144.03 101.99 59.35 not rated
60 270.74 228.06 185.83 143.93 102.11 59.63

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 49.72 not rated not rated not rated not rated not rated
40 86.37 49.98 not rated not rated not rated not rated
45 122.05 86.37 50.21 not rated not rated not rated
50 157.42 121.82 86.37 50.42 not rated not rated
55 192.65 156.99 121.64 86.41 50.63 not rated
60 227.79 192.01 156.63 121.54 86.51 50.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 101.861 17.68 41.5
Low speed (Y) 86.372 14.99 30.8

Dimensions

Dimension drawing of BC/BD-363CC5-B19 C
Dimension drawing
Dimensions as drawn
A 3000 mm
B 1200 mm
C 1240 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 1190 mm
K 3300 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3300 mm
Width 1240 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.