BC/BD-650BB5-B09 C
102.04 kW
Defrost: None
Product code: BC/BD-363CC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 34,060 m³/h |
|---|---|
| External surface | 313.4 m² |
| Inner volume | 44.1 dm³ |
| Fin material | Aluminium |
| Net weight | 347 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-363CC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 58.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 101.86 | 58.57 | not rated | not rated | not rated | not rated |
| 45 | 144.43 | 101.89 | 58.84 | not rated | not rated | not rated |
| 50 | 186.67 | 144.21 | 101.92 | 59.10 | not rated | not rated |
| 55 | 228.75 | 186.21 | 144.03 | 101.99 | 59.35 | not rated |
| 60 | 270.74 | 228.06 | 185.83 | 143.93 | 102.11 | 59.63 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 49.72 | not rated | not rated | not rated | not rated | not rated |
| 40 | 86.37 | 49.98 | not rated | not rated | not rated | not rated |
| 45 | 122.05 | 86.37 | 50.21 | not rated | not rated | not rated |
| 50 | 157.42 | 121.82 | 86.37 | 50.42 | not rated | not rated |
| 55 | 192.65 | 156.99 | 121.64 | 86.41 | 50.63 | not rated |
| 60 | 227.79 | 192.01 | 156.63 | 121.54 | 86.51 | 50.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 101.861 | 17.68 | 41.5 |
| Low speed (Y) | 86.372 | 14.99 | 30.8 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 3300 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3300 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.