BC/BD-463CC5-B01 C
111.87 kW
Defrost: None
Product code: BC/BD-363CD5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 32,913 m³/h |
|---|---|
| External surface | 391.8 m² |
| Inner volume | 53.7 dm³ |
| Fin material | Aluminium |
| Net weight | 372 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-363CD5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 64.69 | not rated | not rated | not rated | not rated | not rated |
| 40 | 111.87 | 65.01 | not rated | not rated | not rated | not rated |
| 45 | 157.73 | 111.82 | 65.28 | not rated | not rated | not rated |
| 50 | 203.15 | 157.38 | 111.78 | 65.53 | not rated | not rated |
| 55 | 248.39 | 202.51 | 157.09 | 111.80 | 65.79 | not rated |
| 60 | 293.51 | 247.47 | 201.98 | 156.88 | 111.90 | 66.09 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.37 | not rated | not rated | not rated | not rated | not rated |
| 40 | 93.29 | 54.62 | not rated | not rated | not rated | not rated |
| 45 | 131.01 | 93.23 | 54.84 | not rated | not rated | not rated |
| 50 | 168.34 | 130.68 | 93.17 | 55.06 | not rated | not rated |
| 55 | 205.49 | 167.76 | 130.42 | 93.18 | 55.29 | not rated |
| 60 | 242.54 | 204.68 | 167.30 | 130.26 | 93.27 | 55.55 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 111.868 | 19.42 | 37.1 |
| Low speed (Y) | 93.292 | 16.19 | 26.7 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 3300 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3300 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.