Skip to Content

Dry cooler BC/BD-380AB1-B01 C

Dry cooler BC/BD-380AB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380AB1-B01 C

Heat rejection i
138.92 kW
Air flow
52,825 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 52,825 m³/h
External surface 370.7 m²
Inner volume 48.3 dm³
Fin materialAluminium
Net weight 503 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-380AB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
138.917 kW Fluid flow 24.11 m³/h Pressure drop 58.6 kPa
Heat rejection · Low speed (Y)
112.146 kW Fluid flow 19.46 m³/h Pressure drop 40.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 78.66 not rated not rated not rated not rated not rated
40 138.92 79.22 not rated not rated not rated not rated
45 197.96 139.21 79.72 not rated not rated not rated
50 256.62 198.02 139.50 80.19 not rated not rated
55 315.09 256.46 198.13 139.81 80.65 not rated
60 373.46 314.72 256.39 198.32 140.20 81.15

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 64.04 not rated not rated not rated not rated not rated
40 112.15 64.46 not rated not rated not rated not rated
45 159.13 112.31 64.84 not rated not rated not rated
50 205.75 159.07 112.48 65.19 not rated not rated
55 252.21 205.49 159.07 112.68 65.55 not rated
60 298.57 251.75 205.32 159.15 112.96 65.94

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 138.917 24.11 58.6
Low speed (Y) 112.146 19.46 40.1

Dimensions

Dimension drawing of BC/BD-380AB1-B01 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 3700 mm
H 1200 mm
I 1190 mm
K 4250 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3950 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.