Skip to Content

Dry cooler BC/BD-380AC5-B01 C

Dry cooler BC/BD-380AC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380AC5-B01 C

Heat rejection i
140.23 kW
Air flow
50,611 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 50,611 m³/h
External surface 417.9 m²
Inner volume 61.1 dm³
Fin materialAluminium
Net weight 526 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-380AC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
140.227 kW Fluid flow 24.34 m³/h Pressure drop 16.4 kPa
Heat rejection · Low speed (Y)
112.228 kW Fluid flow 19.48 m³/h Pressure drop 10.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 77.00 not rated not rated not rated not rated not rated
40 140.23 78.04 not rated not rated not rated not rated
45 201.70 140.82 78.92 not rated not rated not rated
50 262.63 202.00 141.36 79.71 not rated not rated
55 323.32 262.66 202.29 141.91 80.46 not rated
60 383.87 323.10 262.73 202.66 142.50 81.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 62.09 not rated not rated not rated not rated not rated
40 112.23 62.93 not rated not rated not rated not rated
45 160.66 112.62 63.64 not rated not rated not rated
50 208.56 160.76 112.99 64.27 not rated not rated
55 256.23 208.41 160.90 113.38 64.87 not rated
60 303.76 255.85 208.35 161.12 113.82 65.46

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 140.227 24.34 16.4
Low speed (Y) 112.228 19.48 10.9

Dimensions

Dimension drawing of BC/BD-380AC5-B01 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 3700 mm
H 1200 mm
I 1190 mm
K 4250 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3950 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.