BC/BD-463CC5-B19 C
138.39 kW
Defrost: None
Product code: BC/BD-380HC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 46,594 m³/h |
|---|---|
| External surface | 325.7 m² |
| Inner volume | 44.2 dm³ |
| Fin material | Aluminium |
| Net weight | 471 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.3 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-380HC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 79.86 | not rated | not rated | not rated | not rated | not rated |
| 40 | 138.31 | 80.35 | not rated | not rated | not rated | not rated |
| 45 | 195.43 | 138.58 | 80.81 | not rated | not rated | not rated |
| 50 | 252.14 | 195.53 | 138.88 | 81.26 | not rated | not rated |
| 55 | 308.64 | 252.07 | 195.70 | 139.23 | 81.73 | not rated |
| 60 | 365.04 | 308.42 | 252.12 | 195.99 | 139.69 | 82.23 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 63.19 | not rated | not rated | not rated | not rated | not rated |
| 40 | 108.52 | 63.57 | not rated | not rated | not rated | not rated |
| 45 | 152.69 | 108.70 | 63.93 | not rated | not rated | not rated |
| 50 | 196.49 | 152.73 | 108.93 | 64.29 | not rated | not rated |
| 55 | 240.12 | 196.39 | 152.84 | 109.21 | 64.67 | not rated |
| 60 | 283.65 | 239.89 | 196.41 | 153.07 | 109.57 | 65.10 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 138.306 | 24.00 | 81.8 |
| Low speed (Y) | 108.517 | 18.83 | 53.3 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 3800 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3500 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.