Skip to Content

Dry cooler BC/BD-380HD1-B01 C

Dry cooler BC/BD-380HD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380HD1-B01 C

Heat rejection i
147.82 kW
Air flow
43,304 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 43,304 m³/h
External surface 407.1 m²
Inner volume 51.9 dm³
Fin materialAluminium
Net weight 494 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 88.4 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-380HD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
147.819 kW Fluid flow 25.66 m³/h Pressure drop 63.3 kPa
Heat rejection · Low speed (Y)
113.167 kW Fluid flow 19.63 m³/h Pressure drop 39.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 86.36 not rated not rated not rated not rated not rated
40 147.82 86.86 not rated not rated not rated not rated
45 207.66 148.02 87.32 not rated not rated not rated
50 266.95 207.64 148.27 87.78 not rated not rated
55 326.02 266.72 207.72 148.62 88.28 not rated
60 384.95 325.59 266.66 207.96 149.09 88.85

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 66.78 not rated not rated not rated not rated not rated
40 113.17 67.16 not rated not rated not rated not rated
45 158.20 113.31 67.52 not rated not rated not rated
50 202.77 158.16 113.51 67.90 not rated not rated
55 247.13 202.58 158.24 113.79 68.31 not rated
60 291.38 246.79 202.54 158.46 114.19 68.79

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 147.819 25.66 63.3
Low speed (Y) 113.167 19.63 39.4

Dimensions

Dimension drawing of BC/BD-380HD1-B01 C
Dimension drawing
Dimensions as drawn
A 3500 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 3250 mm
H 1050 mm
I 1180 mm
K 3800 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 3500 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.