BC/BD-2X463BA5-B01 C
137.06 kW
Defrost: None
Product code: BC/BD-380ND1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 29,852 m³/h |
|---|---|
| External surface | 1,235.5 m² |
| Inner volume | 137.7 dm³ |
| Fin material | Aluminium |
| Net weight | 859 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-380ND1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 86.05 | not rated | not rated | not rated | not rated | not rated |
| 40 | 137.01 | 85.62 | not rated | not rated | not rated | not rated |
| 45 | 186.54 | 136.05 | 85.26 | not rated | not rated | not rated |
| 50 | 235.63 | 185.11 | 135.24 | 84.98 | not rated | not rated |
| 55 | 284.52 | 233.73 | 183.89 | 134.60 | 84.82 | not rated |
| 60 | 333.30 | 282.17 | 232.12 | 182.93 | 134.19 | 84.81 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 65.51 | not rated | not rated | not rated | not rated | not rated |
| 40 | 103.31 | 65.23 | not rated | not rated | not rated | not rated |
| 45 | 140.05 | 102.66 | 65.01 | not rated | not rated | not rated |
| 50 | 176.47 | 139.08 | 102.15 | 64.86 | not rated | not rated |
| 55 | 212.75 | 175.19 | 138.31 | 101.78 | 64.81 | not rated |
| 60 | 248.95 | 211.17 | 174.17 | 137.75 | 101.59 | 64.89 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 137.005 | 23.76 | 96.2 |
| Low speed (Y) | 103.306 | 17.92 | 58.3 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 7850 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 7850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.