Dry cooler BC/BD-380ND1-B03 C

Dry cooler BC/BD-380ND1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380ND1-B03 C

Heat rejection i
137.01 kW
Air flow
29,852 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 29,852 m³/h
External surface 1,235.5 m²
Inner volume 137.7 dm³
Fin materialAluminium
Net weight 859 kg
Fans
Quantity 3
Diameter 800 mm
Speed 435 rpm
Power 1,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 37.0 dB(A)
Sound power 69.0 dB(A)
Energy class B
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-380ND1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
137.005 kW Fluid flow 23.76 m³/h Pressure drop 96.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
103.306 kW Fluid flow 17.92 m³/h Pressure drop 58.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 86.05 not rated not rated not rated not rated not rated
40 137.01 85.62 not rated not rated not rated not rated
45 186.54 136.05 85.26 not rated not rated not rated
50 235.63 185.11 135.24 84.98 not rated not rated
55 284.52 233.73 183.89 134.60 84.82 not rated
60 333.30 282.17 232.12 182.93 134.19 84.81

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 65.51 not rated not rated not rated not rated not rated
40 103.31 65.23 not rated not rated not rated not rated
45 140.05 102.66 65.01 not rated not rated not rated
50 176.47 139.08 102.15 64.86 not rated not rated
55 212.75 175.19 138.31 101.78 64.81 not rated
60 248.95 211.17 174.17 137.75 101.59 64.89

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 137.005 23.76 96.2
Low speed (Y) 103.306 17.92 58.3

Dimensions

Dimension drawing of BC/BD-380ND1-B03 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 1190 mm
K 7850 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 7850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.