BC/BD-2X263CB5-B19 C
116.65 kW
Defrost: None
Product code: BC/BD-380OB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 31,269 m³/h |
|---|---|
| External surface | 596.2 m² |
| Inner volume | 130.1 dm³ |
| Fin material | Aluminium |
| Net weight | 719 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-380OB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 69.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 116.62 | 69.67 | not rated | not rated | not rated | not rated |
| 45 | 162.34 | 116.22 | 69.65 | not rated | not rated | not rated |
| 50 | 207.65 | 161.59 | 115.88 | 69.67 | not rated | not rated |
| 55 | 252.77 | 206.56 | 160.95 | 115.62 | 69.71 | not rated |
| 60 | 297.78 | 251.35 | 205.63 | 160.45 | 115.48 | 69.84 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 55.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.83 | 55.87 | not rated | not rated | not rated | not rated |
| 45 | 128.73 | 92.49 | 55.86 | not rated | not rated | not rated |
| 50 | 164.28 | 128.11 | 92.21 | 55.87 | not rated | not rated |
| 55 | 199.67 | 163.39 | 127.58 | 92.00 | 55.91 | not rated |
| 60 | 234.97 | 198.52 | 162.63 | 127.18 | 91.88 | 56.01 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 116.620 | 20.23 | 30.1 |
| Low speed (Y) | 92.830 | 16.10 | 20.0 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 7850 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 7850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.