Skip to Content

Dry cooler BC/BD-450BD5-B09 C

Dry cooler BC/BD-450BD5-B09 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-450BD5-B09 C

Heat rejection i
87.20 kW
Air flow
26,287 m³/h
Fans
4 × ⌀500 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 26,287 m³/h
External surface 255.4 m²
Inner volume 35.7 dm³
Fin materialAluminium
Net weight 317 kg
Fans
Quantity 4
Diameter 500 mm
Speed 1,330 rpm
Power 2,800 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 52.0 dB(A)
Sound power 84.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-450BD5-B09 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
87.199 kW Fluid flow 15.13 m³/h Pressure drop 45.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 50.88 not rated not rated not rated not rated not rated
40 87.20 51.09 not rated not rated not rated not rated
45 122.58 87.19 51.29 not rated not rated not rated
50 157.65 122.37 87.19 51.47 not rated not rated
55 192.58 157.26 122.22 87.24 51.68 not rated
60 227.42 192.01 156.97 122.16 87.37 51.91

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 87.199 15.13 45.3

Dimensions

Dimension drawing of BC/BD-450BD5-B09 C
Dimension drawing
Dimensions as drawn
A 3550 mm
B 1220 mm
C 930 mm
F 1050 mm
G 450 mm
E 3300 mm
H 800 mm
I 880 mm
K 3800 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3550 mm
Width 960 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.