Skip to Content

Dry cooler BC/BD-463BC1-B19 C

Dry cooler BC/BD-463BC1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-463BC1-B19 C

Heat rejection i
141.70 kW
Air flow
45,028 m³/h
Fans
4 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 45,028 m³/h
External surface 372.2 m²
Inner volume 48.6 dm³
Fin materialAluminium
Net weight 402 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-463BC1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
141.701 kW Fluid flow 24.60 m³/h Pressure drop 96.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
118.814 kW Fluid flow 20.62 m³/h Pressure drop 70.7 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 82.72 not rated not rated not rated not rated not rated
40 141.70 82.94 not rated not rated not rated not rated
45 199.33 141.56 83.14 not rated not rated not rated
50 256.51 198.86 141.46 83.34 not rated not rated
55 313.49 255.74 198.49 141.43 83.58 not rated
60 370.36 312.41 255.11 198.25 141.50 83.86

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 69.77 not rated not rated not rated not rated not rated
40 118.81 69.96 not rated not rated not rated not rated
45 166.63 118.68 70.12 not rated not rated not rated
50 214.04 166.22 118.57 70.29 not rated not rated
55 261.26 213.36 165.87 118.54 70.48 not rated
60 308.39 260.33 212.79 165.65 118.59 70.73

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 141.701 24.60 96.5
Low speed (Y) 118.814 20.62 70.7

Dimensions

Dimension drawing of BC/BD-463BC1-B19 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 1180 mm
K 4200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 3950 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.