BC/BD-t-2x191OB1-B04 C
130.28 kW
Defrost: None
Product code: BC/BD-463BC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 45,729 m³/h |
|---|---|
| External surface | 315.3 m² |
| Inner volume | 48.6 dm³ |
| Fin material | Aluminium |
| Net weight | 395 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-463BC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 75.59 | not rated | not rated | not rated | not rated | not rated |
| 40 | 130.32 | 75.83 | not rated | not rated | not rated | not rated |
| 45 | 183.89 | 130.27 | 76.05 | not rated | not rated | not rated |
| 50 | 237.07 | 183.57 | 130.24 | 76.27 | not rated | not rated |
| 55 | 290.09 | 236.50 | 183.31 | 130.25 | 76.50 | not rated |
| 60 | 343.01 | 289.26 | 236.03 | 183.15 | 130.35 | 76.76 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 64.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 110.22 | 64.47 | not rated | not rated | not rated | not rated |
| 45 | 155.11 | 110.15 | 64.65 | not rated | not rated | not rated |
| 50 | 199.66 | 154.81 | 110.11 | 64.83 | not rated | not rated |
| 55 | 244.06 | 199.13 | 154.56 | 110.11 | 65.02 | not rated |
| 60 | 288.36 | 243.30 | 198.70 | 154.42 | 110.19 | 65.26 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 130.323 | 22.62 | 83.2 |
| Low speed (Y) | 110.218 | 19.13 | 61.9 |
| A | 3950 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3700 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 4200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3950 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.