BC/BD-680HA1-B01 C
185.58 kW
Defrost: None
Product code: BC/BD-480AC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 63,814 m³/h |
|---|---|
| External surface | 557.2 m² |
| Inner volume | 81.6 dm³ |
| Fin material | Aluminium |
| Net weight | 685 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 7,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-480AC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 104.96 | not rated | not rated | not rated | not rated | not rated |
| 40 | 185.53 | 105.79 | not rated | not rated | not rated | not rated |
| 45 | 264.14 | 185.90 | 106.54 | not rated | not rated | not rated |
| 50 | 342.13 | 264.13 | 186.26 | 107.22 | not rated | not rated |
| 55 | 419.81 | 341.76 | 264.18 | 186.67 | 107.89 | not rated |
| 60 | 497.34 | 419.11 | 341.53 | 264.37 | 187.17 | 108.59 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 185.531 | 32.20 | 28.1 |
| A | 5150 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4900 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 5450 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5150 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.