BC/BD-t-663AA5-B19 C
149.59 kW
Defrost: None
Product code: BC/BD-480CC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 38,589 m³/h |
|---|---|
| External surface | 812.2 m² |
| Inner volume | 108.4 dm³ |
| Fin material | Aluminium |
| Net weight | 821 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-480CC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 90.36 | not rated | not rated | not rated | not rated | not rated |
| 40 | 149.62 | 90.29 | not rated | not rated | not rated | not rated |
| 45 | 207.37 | 149.11 | 90.24 | not rated | not rated | not rated |
| 50 | 264.61 | 206.46 | 148.70 | 90.24 | not rated | not rated |
| 55 | 321.62 | 263.31 | 205.71 | 148.41 | 90.29 | not rated |
| 60 | 378.49 | 319.94 | 262.23 | 205.15 | 148.29 | 90.46 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 70.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 115.64 | 70.41 | not rated | not rated | not rated | not rated |
| 45 | 159.53 | 115.19 | 70.35 | not rated | not rated | not rated |
| 50 | 203.00 | 158.75 | 114.84 | 70.34 | not rated | not rated |
| 55 | 246.28 | 201.91 | 158.13 | 114.60 | 70.41 | not rated |
| 60 | 289.46 | 244.89 | 201.03 | 157.69 | 114.51 | 70.55 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 149.620 | 25.95 | 76.4 |
| Low speed (Y) | 115.641 | 20.06 | 48.4 |
| A | 7350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7100 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 7650 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 7650 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.