BC/BD-491KD5-B04 C
254.46 kW
Defrost: None
Product code: BC/BD-480FC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 74,217 m³/h |
|---|---|
| External surface | 772.4 m² |
| Inner volume | 177.3 dm³ |
| Fin material | Aluminium |
| Net weight | 858 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.5 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-480FC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 150.41 | not rated | not rated | not rated | not rated | not rated |
| 40 | 254.69 | 150.74 | not rated | not rated | not rated | not rated |
| 45 | 356.49 | 254.43 | 151.05 | not rated | not rated | not rated |
| 50 | 457.42 | 355.69 | 254.27 | 151.41 | not rated | not rated |
| 55 | 558.01 | 456.12 | 355.07 | 254.26 | 151.83 | not rated |
| 60 | 658.39 | 556.21 | 455.11 | 354.75 | 254.49 | 152.39 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 118.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 197.88 | 118.17 | not rated | not rated | not rated | not rated |
| 45 | 275.68 | 197.51 | 118.33 | not rated | not rated | not rated |
| 50 | 352.78 | 274.83 | 197.24 | 118.53 | not rated | not rated |
| 55 | 429.56 | 351.48 | 274.17 | 197.11 | 118.81 | not rated |
| 60 | 506.15 | 427.81 | 350.45 | 273.76 | 197.20 | 119.22 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 254.692 | 44.20 | 64.5 |
| Low speed (Y) | 197.881 | 34.32 | 41.2 |
| A | 7350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7100 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 7650 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7650 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.