Skip to Content

Dry cooler BC/BD-480FD1-B01 C

Dry cooler BC/BD-480FD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-480FD1-B01 C

Heat rejection i
284.86 kW
Air flow
68,825 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 68,825 m³/h
External surface 1,140.2 m²
Inner volume 217.6 dm³
Fin materialAluminium
Net weight 955 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 87.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-480FD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
284.860 kW Fluid flow 49.40 m³/h Pressure drop 113.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
215.275 kW Fluid flow 37.34 m³/h Pressure drop 69.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 173.76 not rated not rated not rated not rated not rated
40 284.86 173.63 not rated not rated not rated not rated
45 392.93 283.94 173.55 not rated not rated not rated
50 500.00 391.29 283.22 173.61 not rated not rated
55 606.60 497.67 390.00 282.80 173.83 not rated
60 712.94 603.59 495.82 389.15 282.76 174.29

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 132.78 not rated not rated not rated not rated not rated
40 215.28 132.58 not rated not rated not rated not rated
45 295.38 214.42 132.44 not rated not rated not rated
50 374.71 293.94 213.75 132.41 not rated not rated
55 453.67 372.71 292.80 213.33 132.53 not rated
60 532.44 451.13 371.11 292.02 213.21 132.86

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 284.860 49.40 113.8
Low speed (Y) 215.275 37.34 69.4

Dimensions

Dimension drawing of BC/BD-480FD1-B01 C
Dimension drawing
Dimensions as drawn
A 7350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 1190 mm
K 7650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.