Skip to Content

Dry cooler BC/BD-480HA5-B01 C

Dry cooler BC/BD-480HA5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-480HA5-B01 C

Heat rejection i
104.51 kW
Air flow
75,901 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): A — 2 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 75,901 m³/h
External surface 183.9 m²
Inner volume 33.9 dm³
Fin materialAluminium
Net weight 549 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.2 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-480HA5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
104.513 kW Fluid flow 18.14 m³/h Pressure drop 11.7 kPa
Heat rejection · Low speed (Y)
86.506 kW Fluid flow 15.01 m³/h Pressure drop 8.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 53.96 not rated not rated not rated not rated not rated
40 104.51 55.18 not rated not rated not rated not rated
45 153.84 105.40 56.22 not rated not rated not rated
50 202.91 154.58 106.19 57.11 not rated not rated
55 251.87 203.52 155.25 106.90 57.89 not rated
60 300.75 252.37 204.10 155.87 107.56 58.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 44.67 not rated not rated not rated not rated not rated
40 86.51 45.74 not rated not rated not rated not rated
45 127.07 87.22 46.64 not rated not rated not rated
50 167.35 127.62 87.86 47.41 not rated not rated
55 207.50 167.78 128.13 88.44 48.08 not rated
60 247.59 207.83 168.20 128.63 88.99 48.70

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 104.513 18.14 11.7
Low speed (Y) 86.506 15.01 8.3

Dimensions

Dimension drawing of BC/BD-480HA5-B01 C
Dimension drawing
Dimensions as drawn
A 4550 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 1180 mm
K 4850 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4550 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.