Skip to Content

Dry cooler BC/BD-480NB5-B01 C

Dry cooler BC/BD-480NB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-480NB5-B01 C

Heat rejection i
240.74 kW
Air flow
85,513 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 85,513 m³/h
External surface 835.7 m²
Inner volume 125.2 dm³
Fin materialAluminium
Net weight 935 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-480NB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
240.735 kW Fluid flow 41.78 m³/h Pressure drop 20.0 kPa
Heat rejection · Low speed (Y)
194.199 kW Fluid flow 33.70 m³/h Pressure drop 13.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 135.90 not rated not rated not rated not rated not rated
40 240.74 136.81 not rated not rated not rated not rated
45 343.03 240.84 137.58 not rated not rated not rated
50 444.50 342.44 240.91 138.25 not rated not rated
55 545.62 443.28 341.93 241.02 138.86 not rated
60 646.51 543.78 442.23 341.56 241.23 139.52

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 110.42 not rated not rated not rated not rated not rated
40 194.20 111.14 not rated not rated not rated not rated
45 275.61 194.18 111.74 not rated not rated not rated
50 356.24 274.99 194.17 112.27 not rated not rated
55 436.55 355.09 274.46 194.19 112.78 not rated
60 516.66 434.86 354.08 274.06 194.31 113.31

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 240.735 41.78 20.0
Low speed (Y) 194.199 33.70 13.6

Dimensions

Dimension drawing of BC/BD-480NB5-B01 C
Dimension drawing
Dimensions as drawn
A 9950 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 1190 mm
K 10250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10250 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.