BC/BD-2X563CC1-B01 C
288.44 kW
Defrost: None
Product code: BC/BD-480NC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 83,343 m³/h |
|---|---|
| External surface | 1,114.3 m² |
| Inner volume | 159.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,018 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-480NC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 171.33 | not rated | not rated | not rated | not rated | not rated |
| 40 | 288.41 | 171.31 | not rated | not rated | not rated | not rated |
| 45 | 402.73 | 287.56 | 171.31 | not rated | not rated | not rated |
| 50 | 516.11 | 401.10 | 286.81 | 171.33 | not rated | not rated |
| 55 | 629.12 | 513.72 | 399.64 | 286.26 | 171.45 | not rated |
| 60 | 741.88 | 625.97 | 511.66 | 398.56 | 285.96 | 171.73 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 136.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 227.04 | 136.09 | not rated | not rated | not rated | not rated |
| 45 | 315.62 | 226.26 | 136.03 | not rated | not rated | not rated |
| 50 | 403.43 | 314.21 | 225.62 | 136.04 | not rated | not rated |
| 55 | 490.88 | 401.40 | 313.02 | 225.14 | 136.13 | not rated |
| 60 | 578.14 | 488.24 | 399.68 | 312.11 | 224.91 | 136.32 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 288.406 | 50.05 | 100.8 |
| Low speed (Y) | 227.039 | 39.38 | 65.9 |
| A | 9950 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9700 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 10250 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 10250 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.