Product code: BC/BD-491GB5-B04 C

Heat rejection i
285.37 kW
Air flow
111,425 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 111,425 m³/h
External surface 835.7 m²
Inner volume 125.2 dm³
Fin materialAluminium
Net weight 956 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-491GB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
285.367 kW Fluid flow 49.53 m³/h Pressure drop 27.2 kPa
Heat rejection · Low speed (Y)
234.279 kW Fluid flow 40.66 m³/h Pressure drop 19.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 160.11 not rated not rated not rated not rated not rated
40 285.37 161.30 not rated not rated not rated not rated
45 407.91 285.71 162.29 not rated not rated not rated
50 529.62 407.55 286.01 163.17 not rated not rated
55 650.92 528.60 407.26 286.34 164.01 not rated
60 772.00 649.27 527.74 407.10 286.78 164.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 132.38 not rated not rated not rated not rated not rated
40 234.28 133.33 not rated not rated not rated not rated
45 333.66 234.49 134.15 not rated not rated not rated
50 432.23 333.25 234.68 134.85 not rated not rated
55 530.44 431.26 332.92 234.91 135.54 not rated
60 628.43 528.91 430.44 332.73 235.24 136.26

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 285.367 49.53 27.2
Low speed (Y) 234.279 40.66 19.1

Dimensions

Dimension drawing of BC/BD-491GB5-B04 C
Dimension drawing
Dimensions as drawn
A 9950 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 1190 mm
K 10250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10250 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.