Skip to Content

Dry cooler BC/BD-491KB1-B04 C

Dry cooler BC/BD-491KB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-491KB1-B04 C

Heat rejection i
216.62 kW
Air flow
96,774 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 96,774 m³/h
External surface 434.3 m²
Inner volume 54.5 dm³
Fin materialAluminium
Net weight 683 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-491KB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
216.621 kW Fluid flow 37.60 m³/h Pressure drop 30.8 kPa
Heat rejection · Low speed (Y)
173.483 kW Fluid flow 30.11 m³/h Pressure drop 20.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 118.28 not rated not rated not rated not rated not rated
40 216.62 119.82 not rated not rated not rated not rated
45 312.79 217.62 121.16 not rated not rated not rated
50 408.33 313.41 218.53 122.34 not rated not rated
55 503.57 408.61 314.02 219.42 123.44 not rated
60 598.67 503.53 408.96 314.71 220.34 124.51

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 95.28 not rated not rated not rated not rated not rated
40 173.48 96.58 not rated not rated not rated not rated
45 249.58 174.28 97.69 not rated not rated not rated
50 325.07 250.05 175.02 98.70 not rated not rated
55 400.27 325.26 250.55 175.75 99.63 not rated
60 475.31 400.21 325.55 251.12 176.54 100.55

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 216.621 37.60 30.8
Low speed (Y) 173.483 30.11 20.6

Dimensions

Dimension drawing of BC/BD-491KB1-B04 C
Dimension drawing
Dimensions as drawn
A 5950 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 5700 mm
H 1400 mm
I 1180 mm
K 6250 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 6250 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.