Skip to Content

Dry cooler BC/BD-550CB5-B09 C

Dry cooler BC/BD-550CB5-B09 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-550CB5-B09 C

Heat rejection i
75.40 kW
Air flow
33,373 m³/h
Fans
5 × ⌀500 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 33,373 m³/h
External surface 202.1 m²
Inner volume 35.0 dm³
Fin materialAluminium
Net weight 352 kg
Fans
Quantity 5
Diameter 500 mm
Speed 1,330 rpm
Power 3,600 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 53.0 dB(A)
Sound power 85.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-550CB5-B09 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
75.397 kW Fluid flow 13.09 m³/h Pressure drop 10.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 40.42 not rated not rated not rated not rated not rated
40 75.40 41.07 not rated not rated not rated not rated
45 109.52 75.81 41.62 not rated not rated not rated
50 143.40 109.77 76.18 42.11 not rated not rated
55 177.18 143.51 110.01 76.53 42.56 not rated
60 210.89 177.16 143.64 110.27 76.88 42.97

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 75.397 13.09 10.4

Dimensions

Dimension drawing of BC/BD-550CB5-B09 C
Dimension drawing
Dimensions as drawn
A 3550 mm
B 1200 mm
C 920 mm
F 1050 mm
G 450 mm
E 3350 mm
H 650 mm
I 870 mm
K 3850 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 3850 mm
Width 920 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.