BC/BD-2X263CD1-B01 C
123.24 kW
Defrost: None
Product code: BC/BD-563CA1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 60,564 m³/h |
|---|---|
| External surface | 308.9 m² |
| Inner volume | 45.4 dm³ |
| Fin material | Aluminium |
| Net weight | 475 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-563CA1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 68.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 123.22 | 68.62 | not rated | not rated | not rated | not rated |
| 45 | 177.47 | 123.54 | 69.14 | not rated | not rated | not rated |
| 50 | 231.45 | 177.54 | 123.81 | 69.60 | not rated | not rated |
| 55 | 285.29 | 231.29 | 177.61 | 124.08 | 70.02 | not rated |
| 60 | 339.05 | 284.90 | 231.15 | 177.71 | 124.36 | 70.43 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 59.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 108.01 | 60.43 | not rated | not rated | not rated | not rated |
| 45 | 155.21 | 108.27 | 60.88 | not rated | not rated | not rated |
| 50 | 202.13 | 155.25 | 108.51 | 61.29 | not rated | not rated |
| 55 | 248.93 | 201.97 | 155.31 | 108.75 | 61.67 | not rated |
| 60 | 295.66 | 248.56 | 201.85 | 155.40 | 109.01 | 62.04 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 123.218 | 21.39 | 37.4 |
| Low speed (Y) | 108.005 | 18.74 | 29.6 |
| A | 4800 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 5100 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5100 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.