BC/BD-280NB1-B01 C
135.32 kW
Defrost: None
Product code: BC/BD-563CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 41,712 m³/h |
|---|---|
| External surface | 522.3 m² |
| Inner volume | 77.3 dm³ |
| Fin material | Aluminium |
| Net weight | 549 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,000 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 81.1 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-563CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 76.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 135.29 | 77.45 | not rated | not rated | not rated | not rated |
| 45 | 191.98 | 135.41 | 77.97 | not rated | not rated | not rated |
| 50 | 248.11 | 191.73 | 135.53 | 78.44 | not rated | not rated |
| 55 | 303.98 | 247.51 | 191.54 | 135.71 | 78.90 | not rated |
| 60 | 359.69 | 303.06 | 247.03 | 191.46 | 135.95 | 79.39 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 135.293 | 23.48 | 15.2 |
| A | 4800 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 5100 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5100 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.