Skip to Content

Dry cooler BC/BD-563CD5-B19 C

Dry cooler BC/BD-563CD5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-563CD5-B19 C

Heat rejection i
183.63 kW
Air flow
54,855 m³/h
Fans
5 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 54,855 m³/h
External surface 652.9 m²
Inner volume 93.3 dm³
Fin materialAluminium
Net weight 588 kg
Fans
Quantity 5
Diameter 630 mm
Speed 1,330 rpm
Power 6,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-563CD5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
183.628 kW Fluid flow 31.87 m³/h Pressure drop 19.5 kPa
Heat rejection · Low speed (Y)
153.250 kW Fluid flow 26.60 m³/h Pressure drop 14.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 104.61 not rated not rated not rated not rated not rated
40 183.63 105.38 not rated not rated not rated not rated
45 260.24 183.72 106.03 not rated not rated not rated
50 336.07 259.80 183.82 106.63 not rated not rated
55 411.51 335.11 259.44 183.96 107.20 not rated
60 486.78 410.11 334.33 259.20 184.23 107.82

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 87.94 not rated not rated not rated not rated not rated
40 153.25 88.59 not rated not rated not rated not rated
45 216.28 153.28 89.15 not rated not rated not rated
50 278.61 215.85 153.34 89.65 not rated not rated
55 340.60 277.75 215.51 153.44 90.16 not rated
60 402.41 339.34 277.07 215.34 153.68 90.70

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 183.628 31.87 19.5
Low speed (Y) 153.250 26.60 14.1

Dimensions

Dimension drawing of BC/BD-563CD5-B19 C
Dimension drawing
Dimensions as drawn
A 4800 mm
B 1200 mm
C 1240 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 1190 mm
K 5100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5100 mm
Width 1240 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.