BC/BD-t-2x280LB5-B01 C
278.56 kW
Defrost: None
Product code: BC/BD-580AD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 76,501 m³/h |
|---|---|
| External surface | 1,029.6 m² |
| Inner volume | 129.4 dm³ |
| Fin material | Aluminium |
| Net weight | 924 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.5 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-580AD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 163.19 | not rated | not rated | not rated | not rated | not rated |
| 40 | 278.69 | 164.02 | not rated | not rated | not rated | not rated |
| 45 | 390.88 | 278.87 | 164.82 | not rated | not rated | not rated |
| 50 | 501.99 | 390.49 | 279.11 | 165.62 | not rated | not rated |
| 55 | 612.59 | 501.09 | 390.34 | 279.57 | 166.51 | not rated |
| 60 | 722.90 | 611.20 | 500.56 | 390.55 | 280.30 | 167.52 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 126.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 214.10 | 127.52 | not rated | not rated | not rated | not rated |
| 45 | 298.53 | 214.20 | 128.13 | not rated | not rated | not rated |
| 50 | 382.00 | 298.19 | 214.38 | 128.73 | not rated | not rated |
| 55 | 465.04 | 381.28 | 298.06 | 214.71 | 129.40 | not rated |
| 60 | 547.83 | 463.95 | 380.86 | 298.17 | 215.29 | 130.23 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 278.691 | 48.36 | 42.8 |
| Low speed (Y) | 214.101 | 37.13 | 26.7 |
| A | 6350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6100 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 6650 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6650 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.