Skip to Content

Dry cooler BC/BD-580CD1-B01 C

Dry cooler BC/BD-580CD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-580CD1-B01 C

Heat rejection i
353.96 kW
Air flow
90,611 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 90,611 m³/h
External surface 1,501.5 m²
Inner volume 178.2 dm³
Fin materialAluminium
Net weight 1,150 kg
Fans
Quantity 5
Diameter 800 mm
Speed 900 rpm
Power 9,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 87.9 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-580CD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
353.961 kW Fluid flow 61.38 m³/h Pressure drop 91.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
271.043 kW Fluid flow 47.00 m³/h Pressure drop 57.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 212.57 not rated not rated not rated not rated not rated
40 353.96 212.74 not rated not rated not rated not rated
45 491.56 353.17 212.93 not rated not rated not rated
50 627.86 489.88 352.57 213.23 not rated not rated
55 763.55 625.34 488.57 352.27 213.63 not rated
60 898.91 760.21 623.34 487.74 352.37 214.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 164.60 not rated not rated not rated not rated not rated
40 271.04 164.57 not rated not rated not rated not rated
45 374.30 270.13 164.56 not rated not rated not rated
50 476.51 372.62 269.41 164.66 not rated not rated
55 578.22 474.09 371.26 268.95 164.92 not rated
60 679.67 575.09 472.12 370.32 268.89 165.40

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 353.961 61.38 91.6
Low speed (Y) 271.043 47.00 57.1

Dimensions

Dimension drawing of BC/BD-580CD1-B01 C
Dimension drawing
Dimensions as drawn
A 9100 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 1190 mm
K 9400 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 9400 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.