Skip to Content

Dry cooler BC/BD-580DB1-B03 C

Dry cooler BC/BD-580DB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-580DB1-B03 C

Heat rejection i
150.50 kW
Air flow
41,445 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 41,445 m³/h
External surface 586.4 m²
Inner volume 110.1 dm³
Fin materialAluminium
Net weight 801 kg
Fans
Quantity 5
Diameter 800 mm
Speed 435 rpm
Power 1,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 39.0 dB(A)
Sound power 71.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-580DB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
150.495 kW Fluid flow 26.12 m³/h Pressure drop 82.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
116.555 kW Fluid flow 20.21 m³/h Pressure drop 52.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 89.82 not rated not rated not rated not rated not rated
40 150.50 90.00 not rated not rated not rated not rated
45 209.66 150.37 90.18 not rated not rated not rated
50 268.36 209.27 150.30 90.39 not rated not rated
55 326.82 267.70 209.00 150.34 90.65 not rated
60 385.16 325.91 267.23 208.90 150.53 91.01

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 70.23 not rated not rated not rated not rated not rated
40 116.56 70.40 not rated not rated not rated not rated
45 161.67 116.53 70.56 not rated not rated not rated
50 206.37 161.46 116.51 70.70 not rated not rated
55 250.88 205.99 161.29 116.49 70.87 not rated
60 295.29 250.34 205.69 161.15 116.62 71.15

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 150.495 26.12 82.4
Low speed (Y) 116.555 20.21 52.3

Dimensions

Dimension drawing of BC/BD-580DB1-B03 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 1190 mm
K 6650 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 6650 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.