BC/BD-t-2X363AC1-B19 C
252.49 kW
Defrost: None
Product code: BC/BD-580DC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 73,145 m³/h |
|---|---|
| External surface | 781.9 m² |
| Inner volume | 156.4 dm³ |
| Fin material | Aluminium |
| Net weight | 883 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 9,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.6 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-580DC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 144.77 | not rated | not rated | not rated | not rated | not rated |
| 40 | 252.33 | 145.87 | not rated | not rated | not rated | not rated |
| 45 | 356.75 | 252.73 | 146.85 | not rated | not rated | not rated |
| 50 | 460.09 | 356.57 | 253.19 | 147.80 | not rated | not rated |
| 55 | 562.98 | 459.44 | 356.60 | 253.77 | 148.76 | not rated |
| 60 | 665.59 | 561.86 | 459.08 | 356.87 | 254.53 | 149.82 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 252.326 | 43.79 | 19.9 |
| A | 6350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6100 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 6650 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6350 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.