Skip to Content

Dry cooler BC/BD-580FC5-B03 C

Dry cooler BC/BD-580FC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-580FC5-B03 C

Heat rejection i
188.71 kW
Air flow
46,274 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 46,274 m³/h
External surface 966.0 m²
Inner volume 204.6 dm³
Fin materialAluminium
Net weight 1,043 kg
Fans
Quantity 5
Diameter 800 mm
Speed 435 rpm
Power 1,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 71.0 dB(A)
Energy class B
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-580FC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
188.706 kW Fluid flow 32.73 m³/h Pressure drop 108.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
144.100 kW Fluid flow 24.99 m³/h Pressure drop 67.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 115.49 not rated not rated not rated not rated not rated
40 188.71 115.29 not rated not rated not rated not rated
45 260.06 188.00 115.14 not rated not rated not rated
50 330.80 258.88 187.42 115.05 not rated not rated
55 401.25 329.16 257.90 187.00 115.09 not rated
60 471.56 399.17 327.79 257.17 186.82 115.28

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 89.03 not rated not rated not rated not rated not rated
40 144.10 88.77 not rated not rated not rated not rated
45 197.70 143.38 88.60 not rated not rated not rated
50 250.83 196.56 142.86 88.51 not rated not rated
55 303.73 249.27 195.71 142.50 88.52 not rated
60 356.51 301.77 248.11 195.10 142.34 88.66

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 188.706 32.73 108.3
Low speed (Y) 144.100 24.99 67.0

Dimensions

Dimension drawing of BC/BD-580FC5-B03 C
Dimension drawing
Dimensions as drawn
A 9100 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 1190 mm
K 9400 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 9400 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.