BC/BD-2X650BB5-B09 C
202.38 kW
Defrost: None
Product code: BC/BD-580HC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 80,246 m³/h |
|---|---|
| External surface | 459.8 m² |
| Inner volume | 74.2 dm³ |
| Fin material | Aluminium |
| Net weight | 746 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 88.8 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-580HC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 110.30 | not rated | not rated | not rated | not rated | not rated |
| 40 | 202.52 | 112.05 | not rated | not rated | not rated | not rated |
| 45 | 292.05 | 203.66 | 113.56 | not rated | not rated | not rated |
| 50 | 380.78 | 292.81 | 204.70 | 114.90 | not rated | not rated |
| 55 | 469.18 | 381.26 | 293.60 | 205.74 | 116.15 | not rated |
| 60 | 557.37 | 469.38 | 381.83 | 294.47 | 206.82 | 117.36 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 88.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 161.20 | 89.65 | not rated | not rated | not rated | not rated |
| 45 | 231.61 | 162.10 | 90.94 | not rated | not rated | not rated |
| 50 | 301.24 | 232.19 | 162.95 | 92.08 | not rated | not rated |
| 55 | 370.56 | 301.57 | 232.80 | 163.79 | 93.15 | not rated |
| 60 | 439.68 | 370.67 | 302.02 | 233.51 | 164.69 | 94.20 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 202.522 | 35.15 | 13.9 |
| Low speed (Y) | 161.204 | 27.98 | 9.2 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5600 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.