BC/BD-t-2X263AD5-B01 C
131.59 kW
Defrost: None
Product code: BC/BD-580HC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 39,905 m³/h |
|---|---|
| External surface | 459.8 m² |
| Inner volume | 61.4 dm³ |
| Fin material | Aluminium |
| Net weight | 726 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 39.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-580HC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 77.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 131.64 | 77.47 | not rated | not rated | not rated | not rated |
| 45 | 184.79 | 131.75 | 77.84 | not rated | not rated | not rated |
| 50 | 237.48 | 184.69 | 131.92 | 78.19 | not rated | not rated |
| 55 | 289.96 | 237.19 | 184.69 | 132.15 | 78.58 | not rated |
| 60 | 342.33 | 289.49 | 237.05 | 184.83 | 132.49 | 79.02 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 60.06 | not rated | not rated | not rated | not rated | not rated |
| 40 | 101.79 | 60.43 | not rated | not rated | not rated | not rated |
| 45 | 142.29 | 101.97 | 60.78 | not rated | not rated | not rated |
| 50 | 182.42 | 142.34 | 102.19 | 61.13 | not rated | not rated |
| 55 | 222.37 | 182.36 | 142.48 | 102.47 | 61.52 | not rated |
| 60 | 262.22 | 222.21 | 182.43 | 142.75 | 102.86 | 61.95 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 131.639 | 22.85 | 43.3 |
| Low speed (Y) | 101.789 | 17.67 | 27.4 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5900 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.