Skip to Content

Dry cooler BC/BD-580HD5-B01 C

Dry cooler BC/BD-580HD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-580HD5-B01 C

Heat rejection i
233.53 kW
Air flow
74,822 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 74,822 m³/h
External surface 574.7 m²
Inner volume 87.0 dm³
Fin materialAluminium
Net weight 779 kg
Fans
Quantity 5
Diameter 800 mm
Speed 900 rpm
Power 9,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 89.8 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-580HD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
233.534 kW Fluid flow 40.54 m³/h Pressure drop 73.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
181.437 kW Fluid flow 31.49 m³/h Pressure drop 46.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 136.08 not rated not rated not rated not rated not rated
40 233.53 136.81 not rated not rated not rated not rated
45 328.71 233.89 137.50 not rated not rated not rated
50 423.14 328.77 234.32 138.19 not rated not rated
55 517.25 422.94 328.99 234.86 138.93 not rated
60 611.15 516.77 422.97 329.43 235.59 139.78

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 106.64 not rated not rated not rated not rated not rated
40 181.44 107.21 not rated not rated not rated not rated
45 254.27 181.70 107.76 not rated not rated not rated
50 326.45 254.30 182.04 108.32 not rated not rated
55 398.36 326.26 254.45 182.48 109.03 not rated
60 470.10 397.96 326.29 254.82 183.25 109.75

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 233.534 40.54 73.3
Low speed (Y) 181.437 31.49 46.9

Dimensions

Dimension drawing of BC/BD-580HD5-B01 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1050 mm
I 1180 mm
K 5900 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5600 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.