BC/BD-780EC5-B01I C
376.52 kW
Defrost: None
Product code: BC/BD-591DC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 118,983 m³/h |
|---|---|
| External surface | 966.0 m² |
| Inner volume | 217.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,090 kg |
| Quantity | 5 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 14,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 98.1 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-591DC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 219.03 | not rated | not rated | not rated | not rated | not rated |
| 40 | 376.60 | 219.85 | not rated | not rated | not rated | not rated |
| 45 | 530.56 | 376.57 | 220.61 | not rated | not rated | not rated |
| 50 | 683.34 | 529.76 | 376.63 | 221.38 | not rated | not rated |
| 55 | 835.56 | 681.81 | 529.20 | 376.92 | 222.24 | not rated |
| 60 | 987.48 | 833.34 | 680.66 | 529.07 | 377.52 | 223.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 171.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 292.26 | 172.30 | not rated | not rated | not rated | not rated |
| 45 | 409.75 | 292.20 | 172.95 | not rated | not rated | not rated |
| 50 | 526.16 | 409.03 | 292.34 | 173.59 | not rated | not rated |
| 55 | 642.13 | 524.91 | 408.76 | 292.59 | 174.30 | not rated |
| 60 | 757.84 | 640.34 | 524.24 | 408.69 | 293.09 | 175.16 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 376.600 | 65.37 | 55.8 |
| Low speed (Y) | 292.258 | 50.72 | 35.5 |
| A | 9100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 9400 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 9400 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.