Dry cooler BC/BD-680AC5-B01 C

Dry cooler BC/BD-680AC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-680AC5-B01 C

Heat rejection i
280.14 kW
Air flow
101,223 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 101,223 m³/h
External surface 835.7 m²
Inner volume 125.2 dm³
Fin materialAluminium
Net weight 1,001 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-680AC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
280.138 kW Fluid flow 48.62 m³/h Pressure drop 14.2 kPa
Heat rejection · Low speed (Y)
224.217 kW Fluid flow 38.91 m³/h Pressure drop 9.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 153.66 not rated not rated not rated not rated not rated
40 280.14 155.77 not rated not rated not rated not rated
45 403.08 281.35 157.55 not rated not rated not rated
50 524.96 403.70 282.44 159.14 not rated not rated
55 646.35 525.03 404.30 283.55 160.65 not rated
60 767.44 645.92 525.19 405.04 284.74 162.13

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 123.92 not rated not rated not rated not rated not rated
40 224.22 125.61 not rated not rated not rated not rated
45 321.09 225.01 127.04 not rated not rated not rated
50 416.89 321.30 225.77 128.32 not rated not rated
55 512.23 416.61 321.59 226.56 129.53 not rated
60 607.31 511.49 416.50 322.04 227.44 130.72

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 280.138 48.62 14.2
Low speed (Y) 224.217 38.91 9.5

Dimensions

Dimension drawing of BC/BD-680AC5-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7300 mm
H 1200 mm
I 1190 mm
K 7850 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7550 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.