Skip to Content

Dry cooler BC/BD-680FB5-B01 C

Dry cooler BC/BD-680FB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-680FB5-B01 C

Heat rejection i
322.66 kW
Air flow
117,580 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 117,580 m³/h
External surface 869.4 m²
Inner volume 198.1 dm³
Fin materialAluminium
Net weight 1,171 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 88.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-680FB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
322.662 kW Fluid flow 56.00 m³/h Pressure drop 16.2 kPa
Heat rejection · Low speed (Y)
256.719 kW Fluid flow 44.56 m³/h Pressure drop 10.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 179.69 not rated not rated not rated not rated not rated
40 322.66 181.43 not rated not rated not rated not rated
45 462.15 323.42 182.92 not rated not rated not rated
50 600.55 462.15 324.12 184.26 not rated not rated
55 738.44 599.82 462.21 324.87 185.53 not rated
60 876.05 737.04 599.28 462.45 325.72 186.80

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 144.06 not rated not rated not rated not rated not rated
40 256.72 145.44 not rated not rated not rated not rated
45 366.11 257.20 146.61 not rated not rated not rated
50 474.48 365.93 257.66 147.68 not rated not rated
55 582.38 473.66 365.82 258.19 148.70 not rated
60 690.00 580.98 473.06 365.91 258.84 149.75

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 322.662 56.00 16.2
Low speed (Y) 256.719 44.56 10.7

Dimensions

Dimension drawing of BC/BD-680FB5-B01 C
Dimension drawing
Dimensions as drawn
A 10850 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 10600 mm
H 1750 mm
I 1190 mm
K 11150 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.