Skip to Content

Dry cooler BC/BD-691DC5-B04 C

Dry cooler BC/BD-691DC5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-691DC5-B04 C

Heat rejection i
456.50 kW
Air flow
142,780 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 142,780 m³/h
External surface 1,159.2 m²
Inner volume 268.5 dm³
Fin materialAluminium
Net weight 1,297 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.1 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-691DC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
456.496 kW Fluid flow 79.23 m³/h Pressure drop 85.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
354.031 kW Fluid flow 61.45 m³/h Pressure drop 54.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 267.71 not rated not rated not rated not rated not rated
40 456.50 268.40 not rated not rated not rated not rated
45 641.09 456.22 269.05 not rated not rated not rated
50 824.32 639.93 456.08 269.79 not rated not rated
55 1006.89 822.30 639.09 456.25 270.64 not rated
60 1189.12 1004.05 820.75 638.75 456.82 271.68

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 209.66 not rated not rated not rated not rated not rated
40 354.03 210.17 not rated not rated not rated not rated
45 494.80 353.75 210.76 not rated not rated not rated
50 634.42 493.82 353.78 211.35 not rated not rated
55 773.50 632.78 493.35 353.96 212.06 not rated
60 912.29 771.23 631.86 493.17 354.42 212.98

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 456.496 79.23 85.6
Low speed (Y) 354.031 61.45 54.6

Dimensions

Dimension drawing of BC/BD-691DC5-B04 C
Dimension drawing
Dimensions as drawn
A 11050 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 10600 mm
H 1750 mm
I 1190 mm
K 11550 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 11550 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.