BC/BD-550DB5-B09 C
86.79 kW
Defrost: None
Product code: BC/BD-750BA5-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 52,184 m³/h |
|---|---|
| External surface | 178.8 m² |
| Inner volume | 27.5 dm³ |
| Fin material | Aluminium |
| Net weight | 446 kg |
| Quantity | 7 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 5,000 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.5 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-750BA5-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 46.90 | not rated | not rated | not rated | not rated | not rated |
| 40 | 86.77 | 47.53 | not rated | not rated | not rated | not rated |
| 45 | 125.80 | 87.15 | 48.06 | not rated | not rated | not rated |
| 50 | 164.62 | 126.03 | 87.49 | 48.52 | not rated | not rated |
| 55 | 203.34 | 164.71 | 126.24 | 87.81 | 48.93 | not rated |
| 60 | 242.01 | 203.30 | 164.80 | 126.45 | 88.12 | 49.32 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 86.771 | 15.06 | 19.0 |
| A | 5950 mm |
|---|---|
| B | 1220 mm |
| C | 930 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 5700 mm |
| H | 800 mm |
| I | 880 mm |
| K | 6200 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5950 mm |
|---|---|
| Width | 960 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.