BC/BD-t-580GB5-B01 C
211.82 kW
Defrost: None
Product code: BC/BD-763BD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 55,047 m³/h |
|---|---|
| External surface | 814.2 m² |
| Inner volume | 99.8 dm³ |
| Fin material | Aluminium |
| Net weight | 719 kg |
| Quantity | 7 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 4,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-763BD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 127.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 211.82 | 127.19 | not rated | not rated | not rated | not rated |
| 45 | 294.31 | 211.39 | 127.35 | not rated | not rated | not rated |
| 50 | 376.03 | 293.38 | 211.10 | 127.57 | not rated | not rated |
| 55 | 457.40 | 374.62 | 292.67 | 210.97 | 127.85 | not rated |
| 60 | 538.57 | 455.52 | 373.52 | 292.24 | 211.07 | 128.30 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 211.816 | 36.74 | 73.1 |
| A | 6750 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 6400 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 7100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6750 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.