Dry cooler BC/BD-791EB5-B04 C

Dry cooler BC/BD-791EB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-791EB5-B04 C

Heat rejection i
372.66 kW
Air flow
171,422 m³/h
Fans
7 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 171,422 m³/h
External surface 853.1 m²
Inner volume 127.3 dm³
Fin materialAluminium
Net weight 1,209 kg
Fans
Quantity 7
Diameter 910 mm
Speed 840 rpm
Power 19,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-791EB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
372.656 kW Fluid flow 64.68 m³/h Pressure drop 44.6 kPa
Heat rejection · Low speed (Y)
303.766 kW Fluid flow 52.72 m³/h Pressure drop 30.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 207.62 not rated not rated not rated not rated not rated
40 372.66 209.45 not rated not rated not rated not rated
45 534.77 373.84 211.07 not rated not rated not rated
50 695.99 535.40 374.94 212.54 not rated not rated
55 856.78 696.10 536.06 376.05 213.95 not rated
60 1017.34 856.40 696.36 536.86 377.24 215.37

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 170.47 not rated not rated not rated not rated not rated
40 303.77 172.00 not rated not rated not rated not rated
45 434.28 304.69 173.34 not rated not rated not rated
50 563.91 434.73 305.57 174.57 not rated not rated
55 693.18 563.95 435.25 306.49 175.77 not rated
60 822.19 692.78 564.14 435.93 307.53 176.98

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 372.656 64.68 44.6
Low speed (Y) 303.766 52.72 30.9

Dimensions

Dimension drawing of BC/BD-791EB5-B04 C
Dimension drawing
Dimensions as drawn
A 10150 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 9900 mm
H 1400 mm
I 1190 mm
K 10450 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10450 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.