Skip to Content

Dry cooler BC/BD-880EB1-B01 C

Dry cooler BC/BD-880EB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-880EB1-B01 C

Heat rejection i
413.93 kW
Air flow
141,963 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 141,963 m³/h
External surface 1,094.6 m²
Inner volume 209.8 dm³
Fin materialAluminium
Net weight 1,393 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-880EB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
413.926 kW Fluid flow 71.85 m³/h Pressure drop 26.6 kPa
Heat rejection · Low speed (Y)
328.054 kW Fluid flow 56.94 m³/h Pressure drop 17.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 232.51 not rated not rated not rated not rated not rated
40 413.93 234.57 not rated not rated not rated not rated
45 590.97 414.92 236.39 not rated not rated not rated
50 766.61 591.07 415.88 238.09 not rated not rated
55 941.56 765.89 591.33 416.99 239.79 not rated
60 1116.14 940.07 765.49 591.95 418.36 241.54

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 185.95 not rated not rated not rated not rated not rated
40 328.05 187.50 not rated not rated not rated not rated
45 466.13 328.60 188.87 not rated not rated not rated
50 602.90 465.90 329.17 190.17 not rated not rated
55 739.06 601.93 465.81 329.89 191.44 not rated
60 874.89 737.39 601.25 466.09 330.78 192.76

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 413.926 71.85 26.6
Low speed (Y) 328.054 56.94 17.4

Dimensions

Dimension drawing of BC/BD-880EB1-B01 C
Dimension drawing
Dimensions as drawn
A 11750 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 11300 mm
H 1400 mm
I 1190 mm
K 12250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 11750 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.