Skip to Content

Dry cooler BC/BD-t-180GB1-B01 C

Dry cooler BC/BD-t-180GB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-180GB1-B01 C

Heat rejection i
47.19 kW
Air flow
15,884 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 15,884 m³/h
External surface 81.4 m²
Inner volume 11.3 dm³
Fin materialAluminium
Net weight 181 kg
Fans
Quantity 1
Diameter 800 mm
Speed 900 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 50.0 dB(A)
Sound power 82.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-t-180GB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
47.190 kW Fluid flow 8.19 m³/h Pressure drop 48.7 kPa
Heat rejection · Low speed (Y)
37.355 kW Fluid flow 6.48 m³/h Pressure drop 32.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 26.53 not rated not rated not rated not rated not rated
40 47.19 26.79 not rated not rated not rated not rated
45 67.33 47.34 27.02 not rated not rated not rated
50 87.30 67.39 47.49 27.24 not rated not rated
55 107.19 87.28 67.47 47.65 27.45 not rated
60 127.03 107.10 87.31 67.59 47.83 27.67

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 21.21 not rated not rated not rated not rated not rated
40 37.36 21.42 not rated not rated not rated not rated
45 53.02 37.46 21.60 not rated not rated not rated
50 68.53 53.05 37.57 21.78 not rated not rated
55 83.95 68.50 53.11 37.70 21.95 not rated
60 99.35 83.86 68.50 53.20 37.85 22.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 47.190 8.19 48.7
Low speed (Y) 37.355 6.48 32.1

Dimensions

Dimension drawing of BC/BD-t-180GB1-B01 C
Dimension drawing
Dimensions as drawn
A 1400 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 1150 mm
H 1050 mm
I 1180 mm
K 1700 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 1400 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.