BC/BD-180CC5-B03 C
37.18 kW
Defrost: None
Product code: BC/BD-t-180JB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 9,839 m³/h |
|---|---|
| External surface | 114.9 m² |
| Inner volume | 15.5 dm³ |
| Fin material | Aluminium |
| Net weight | 213 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | B |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-t-180JB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 22.13 | not rated | not rated | not rated | not rated | not rated |
| 40 | 37.22 | 22.16 | not rated | not rated | not rated | not rated |
| 45 | 51.88 | 37.12 | 22.18 | not rated | not rated | not rated |
| 50 | 66.39 | 51.67 | 37.03 | 22.21 | not rated | not rated |
| 55 | 80.84 | 66.08 | 51.49 | 36.97 | 22.24 | not rated |
| 60 | 95.26 | 80.43 | 65.81 | 51.35 | 36.95 | 22.30 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 17.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 28.91 | 17.37 | not rated | not rated | not rated | not rated |
| 45 | 40.10 | 28.83 | 17.40 | not rated | not rated | not rated |
| 50 | 51.18 | 39.94 | 28.78 | 17.43 | not rated | not rated |
| 55 | 62.20 | 50.94 | 39.82 | 28.75 | 17.48 | not rated |
| 60 | 73.19 | 61.88 | 50.76 | 39.75 | 28.76 | 17.54 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 37.215 | 6.45 | 50.6 |
| Low speed (Y) | 28.907 | 5.01 | 32.2 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 1180 mm |
| K | 2400 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 2400 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.