BC/BD-2x180HB5-B03 C
46.40 kW
Defrost: None
Product code: BC/BD-t-180LC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 10,159 m³/h |
|---|---|
| External surface | 210.2 m² |
| Inner volume | 26.2 dm³ |
| Fin material | Aluminium |
| Net weight | 264 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | B |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-t-180LC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 28.96 | not rated | not rated | not rated | not rated | not rated |
| 40 | 46.48 | 28.85 | not rated | not rated | not rated | not rated |
| 45 | 63.43 | 46.16 | 28.75 | not rated | not rated | not rated |
| 50 | 80.21 | 62.94 | 45.89 | 28.67 | not rated | not rated |
| 55 | 96.91 | 79.55 | 62.52 | 45.68 | 28.63 | not rated |
| 60 | 113.57 | 96.09 | 78.99 | 62.19 | 45.54 | 28.64 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 22.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 35.52 | 22.27 | not rated | not rated | not rated | not rated |
| 45 | 48.27 | 35.30 | 22.21 | not rated | not rated | not rated |
| 50 | 60.88 | 47.92 | 35.12 | 22.17 | not rated | not rated |
| 55 | 73.43 | 60.42 | 47.64 | 34.98 | 22.15 | not rated |
| 60 | 85.95 | 72.86 | 60.04 | 47.42 | 34.90 | 22.17 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 46.475 | 8.06 | 62.4 |
| Low speed (Y) | 35.523 | 6.16 | 38.6 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 3050 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.